Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776
CounterNo
Jitter, max.1 µs; typically ±
— Number, max.2; 1 per channel
Weight, approx.50 g
— ON period, max.100 %
— ON period, min.0 %
Current-sinkingYes
Power loss, typ.1.7 W
Rated value (DC)24 V
Current-sourcingYes
— parameterizableYes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
usable BaseUnitsBU type B1
Number of outputs2; A common 24V encoder supply for both channels
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
Automatic encodingYes
Diagnostics functionYes
— Amplitude adjustableYes
— Frequency adjustableYes
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Bus cycle time (TDP), min.250 µs; with 1 channel configuration, 375 µs with 2 channel configuration
minimum pulse duration1.5 µs; With High Speed output, 10 µs with Standard output
Type of digital outputP- and M-switching
Current consumption, max.70 mA; without load
Short-circuit protectionYes; electronic/thermal
Number of digital inputs2; 1 per channel
Product type designationTM Pulse 2x24 V
Number of digital outputs2; 1 per channel
Accuracy of pulse duration±100 ppm ±0.5 µs with High Speed output, ±100 ppm ±9 µs with Standard output
Controlling a digital inputYes
Number of RS 485 interfaces0
to standard PROFIBUS masterYes
— Resolution of the duty cycle0.0036 %; For S7 analog format, min. 20 ns
Substitute values connectableYes; Parameterizable
Suitable for safety functionsNo
Digital inputs, parameterizableYes
— Cycle duration, parameterizableYes; Max. 85 s
Digital outputs, parameterizableYes
to standard PROFINET controllerYes
Limitation of inductive shutdown voltage to-0.8 V
Color code for module-specific color-coded labelCC40
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Input characteristic curve in accordance with IEC 61131, type 3Yes
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!