— ParityNone, even, odd, always 1, always 0, any
— Address area1 to 247, extended 1 to 65535
Weight, approx.30 g
Power loss, typ.0.7 W
Rated value (DC)24 V
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
usable BaseUnitsBU type A0
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
Automatic encodingYes
— Bits per character7 or 8
— Number of stop bits1 or 2 bit
— Telegram length, max.2 kbyte; performance mode: receive data max. 24 byte and send data max. 30 byte
Diagnostics functionYes
Isolation tested with707 V DC (type test)
— max. number of devices32
Current consumption, max.35 mA
Product type designationCM PtP
Reverse polarity protectionYes
Current consumption (rated value)31 mA
to standard PROFINET controllerYes
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
between backplane bus and interfaceYes
— global warming potential, (total) [CO2 eq]25.2 kg
— global warming potential, (during operation) [CO2 eq]19.4 kg
— global warming potential, (during production) [CO2 eq]6.15 kg
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— global warming potential, (after end of life cycle) [CO2 eq]-0.289 kg
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!