— CFCNo
— FBDYes
— IRTNo
— LADYes
— MRPYes
— SCLYes
— STLYes
— MRPDYes; Requirement: IRT
— GRAPHYes
PROFIsafeNo
— per probe40
— adjustableYes
— Inputs, max.8 kbyte
Single stepYes
via datasetYes
— Outputs, max.8 kbyte
— PROFIenergyYes
Status blockYes; up to 8 simultaneously
— EquidistanceNo
— per cam track160
— Shared deviceYes
— UDP multicastYes; 128 multicast circuits (of which max. 5 via CP 1625)
Interface typePROFIBUS with CP 5623
Motion ControlYes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER
Program alarmsYes
— per output cam20
— Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
— Data length, max.2 kbyte
Software versionV21.9
— Isochronous modeNo
Hardware requiredSIMATIC IPC2x7E, IPC4x7D/E, IPC6x7D/E, IPC8x7D/E
— Security policiesYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— PG/OP communicationYes
— Prioritized startupYes; max. 32 PROFINET devices; if you want to use the "Prioritized startup" functionality in STEP 7 for the PROFINET interface of the CPU, the CPU and the device must be separated by means of a switch (e.g. SCALANCE X205)
— User authenticationYes; "anonymous" or by user name & password
Number of interfaces3
Number of IO modules8 192
— Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
— of which in line, max.128
— per external encoder80
— per positioning axis80
— per synchronous axis160
— shortest clock pulse500 µs
Number of breakpoints8
Number of connections44
— Sampling interval, min.10 ms
— Transmission rate, max.100 Mbit/s
for bit operations, typ.1 ns; On IPC427E, Intel Xeon processor
— for send cycle of 1 ms1 ms to 512 ms
— for send cycle of 2 ms2 ms to 512 ms
— for send cycle of 4 ms4 ms to 512 ms
— Number of sessions, max.64
for word operations, typ.2 ns; On IPC427E, Intel Xeon processor
— Asset management recordYes
— for send cycle of 250 µs250 µs to 128 ms
— for send cycle of 500 µs500 µs to 256 ms
— of which powerfail-proof300
— Publishing interval, min.10 ms
Number of elements (total)6 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements
Product type designationCPU 1507S
— per speed-controlled axis40
— Number of connections, max.40
— Application authenticationYes
SIMATIC memory card requiredNo; Use of the PC mass storage
— Number of server methods, max.100
Number of PROFIBUS interfaces1
Number of PROFINET interfaces2; Of which one interface can be used as an IO Controller or I-Device
— of which status variables, max.200
for fixed point arithmetic, typ.2 ns; On IPC427E, Intel Xeon processor
— Industrial Ethernet status LEDYes
— of which control variables, max.200
— Number of server interfaces, max.10
Number of distributed IO systems20
— Number of registerable nodes, max.50 000
— Of which IO devices with IRT, max.64
for floating point arithmetic, typ.2 ns; On IPC427E, Intel Xeon processor
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 10 engineering systems
— Number of IO Devices per tool, max.8
— Switchover time on line break, typ.200 ms; For MRP, bumpless for MRPD
— Number of accessible variables, max.200 000
— Number of stations in the ring, max.50
— Number of connectable IO Devices, max.256
— Number of subscriptions per session, max.20
— Number of monitored items, recommended max.10 000; for 1 s sampling interval and 1 s send interval
Number of configurable program messages, max.10 000
— Number of connectable IO Devices for RT, max.128
— Number of inputs/outputs per server method, max.20
Number of loadable program messages in RUN, max.5 000
Number of simultaneously active program alarms1 000
— Number of IO Controllers with shared device, max.4
— With IRT and parameterization of "odd" send cyclesUpdate time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)
Number of login stations for message functions, max.32
Retentive data area (incl. timers, counters, flags), max.135 kbyte; on SIMATIC IPC227E, IPC277E, IPC427D, IPC477D, IPC427E, IPC477E, IPC627E, IPC677E; 35 KB on SIMATIC IPC627D, IPC677D and IPC827D
— Number of nodes for user-defined server interfaces, max.30 000
— Number of nodes of the client interfaces, recommended max.5 000
— Number of inputs/outputs when calling OPC_UA_MethodCall, max.20
Extended retentive data area (incl. timers, counters, flags), max.20 Mbyte; When using PC mass storage for retentive data
— IO Devices changing during operation (partner ports), supportedYes; the CPU and changing IO devices must be separated by a switch (e.g. SCALANCE X205)
— Number of registerable method calls of OPC_UA_MethodCall, max.100
— Number of elements for one call of OPC_UA_MethodGetHandleList, max.100
— Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max.20
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— Number of positioning axes at motion control cycle of 4 ms (typical value)30; On IPC427E, Intel Xeon processor
— Number of positioning axes at motion control cycle of 8 ms (typical value)60; On IPC427E, Intel Xeon processor
— Number of simultaneous calls of the client instructions for data access, per connection, max.5
— Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max.300
— Number of simultaneous calls of the client instructions for session management, per connection, max.1