BISYes
FM approvalYes; Ta: 0 °C to 70 °C T4
Weight, approx.1 300 g
Power loss, typ.35 W
primary/secondaryYes
Inrush current, max.88 A; Full width at half maximum 1.1 ms
Leakage current, max.5 mA
Overvoltage categoryII
Active power input, typ.158 W
Type of output voltageDC
Rated value at 120 V AC1.4 A
Rated value at 120 V DC1.4 A
Rated value at 230 V AC0.7 A
Rated value at 230 V DC0.7 A
Short-circuit protectionYes
Equipment protection classI, with protective conductor
for backplane bus (5 V DC), max.20 A; no base load required
for backplane bus (24 V DC), max.1 A; idling-proof
Design of electrical connection3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm