I²t0.426 A²·s; with starting current inrush
— CFCNo
— FBDYes; incl. failsafe
— IRTYes
— LADYes; incl. failsafe
— MRPYes
— SCLYes
— STLYes
— MRPDYes
— GRAPHYes
SD cardOptionally for additional mass storage
PROFIsafeYes
— per probe40; per probe
— adjustableYes
— Inputs, max.8 kbyte
Main memory8 GB RAM
Single stepNo
via datasetYes
— Outputs, max.8 kbyte
— PROFIenergyYes
AutocrossingYes
Status blockYes; up to 8 simultaneously
— EquidistanceNo
Weight, approx.0.83 kg
— per cam track160; per cam track
— Shared deviceYes
Interface typePROFIBUS with CM DP
Motion ControlYes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool
Power loss, typ.15 W; without ET 200SP modules and without using USB
Processor typeIntel Atom E3940, 1.6 GHz, 4 cores
Program alarmsYes
Rated value (DC)24 V
Type of memoryDDR3L
— per output cam20; per cam
— Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
AutonegotiationYes
— Data length, max.2 048 byte
— Isochronous modeNo
CFast memory cardYes; 30 GB flash memory
— Security policiesYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— Prioritized startupYes
— User authenticationYes; "anonymous" or by user name & password
Mode selector switch1
Number of IO modules8 192
— of which in line, max.128
— per external encoder80; per external encoder
— per positioning axis80; per axis
— per synchronous axis160; per axis
— shortest clock pulse500 µs
Number of breakpoints8
Number of connections44
— Transmission rate, max.1 000 Mbit/s
Active power input, max.55 W; incl. ET 200SP modules and using USB
— for send cycle of 1 ms1 ms to 512 ms
— for send cycle of 2 ms2 ms to 512 ms
— for send cycle of 4 ms4 ms to 512 ms
Current consumption, max.2.9 A
Integrated power supplyYes
Number of SD card slots1
— Asset management recordYes
— for send cycle of 500 µs500 µs to 256 ms
— of which powerfail-proof300
Number of elements (total)6 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements
Number of USB interfaces4; 2x USB 2.0, 2x USB 3.0 on front side
Product type designationCPU 1515SP PC2 F
— per speed-controlled axis40; per axis
— Application authenticationYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
Number of RS 485 interfaces1; Via CM DP module
Reverse polarity protectionYes
SIMATIC memory card requiredNo
Number of PROFIBUS interfaces1
Number of PROFINET interfaces1
pre-installed operating systemWindows 10 IoT Enterprise 2016 LTSB, 64bit, MUI
— of which status variables, max.200
— Industrial Ethernet status LEDNo
— of which control variables, max.200
Current consumption (rated value)1.8 A; Full processor load, incl. ET 200SP modules and using USB
Number of distributed IO systems20
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
— Of which IO devices with IRT, max.64
Infeed power to the backplane bus8.75 W
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 8 engineering systems
— Number of IO Devices per tool, max.8
— Switchover time on line break, typ.200 ms
— Number of stations in the ring, max.50
— Number of connectable IO Devices, max.128
— global warming potential, (total) [CO2 eq]432 kg
automatic detection of transmission rateYes
Number of industrial Ethernet interfaces2
Current consumption (in no-load operation), typ.0.5 A
Number of configurable program messages, max.10 000
— Number of connectable IO Devices for RT, max.128
Number of simultaneously active program alarms1 000
— Low demand mode: PFDavg in accordance with SIL3< 2.00E-05
— Number of IO Controllers with shared device, max.4
— global warming potential, (during operation) [CO2 eq]365 kg
— With IRT and parameterization of "odd" send cyclesUpdate time = set "odd" send clock (any multiple of 125 µs: 625 µs ... 3 875 µs) minimum cycle time start from 500 µs
— global warming potential, (during production) [CO2 eq]73.8 kg
Number of login stations for message functions, max.32
Retentive data area (incl. timers, counters, flags), max.410 kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— High demand/continuous mode: PFH in accordance with SIL3< 1.00E-09 1/h
— global warming potential, (after end of life cycle) [CO2 eq]-6.71 kg
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— IO Devices changing during operation (partner ports), supportedYes
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— Number of positioning axes at motion control cycle of 4 ms (typical value)15
— Number of positioning axes at motion control cycle of 8 ms (typical value)30
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!