I²t0.426 A²·s; with starting current inrush
— CFCNo
— FBDYes
— IRTYes
— LADYes
— MRPYes; MRP Automanager according to IEC 62439-2 Edition 2.0, MRP Manager; MRP Client
— SCLYes
— STLYes
— MRPDYes; Requirement: IRT
— GRAPHYes
SD cardOptionally for additional mass storage
ProfilingNo
PROFIsafeNo
— per probe40
— adjustableYes
— Inputs, max.8 kbyte
Main memory8 GB RAM
Single stepYes
via datasetYes
— Outputs, max.8 kbyte
— PROFIenergyYes; per user program
AutocrossingYes
Status blockYes; up to 8 simultaneously
— EquidistanceNo
Weight, approx.0.83 kg
— per cam track160
— Shared deviceYes
— UDP multicastYes; Max. 5 multicast circuits
Interface typePROFIBUS with CM DP
Motion ControlYes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER
Power loss, typ.16 W
Processor typeIntel Atom E3940, 1.6 GHz, 4 cores
Program alarmsYes
Rated value (DC)24 V
Type of memoryDDR3L
— per output cam20
— Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
AutonegotiationYes
— Data length, max.2 kbyte; 1 472 bytes for UDP broadcast
— Isochronous modeNo
— Media redundancyYes; only via BusAdapter
CFast memory cardYes; 128 GB flash memory
— Security policiesYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— Prioritized startupYes
— User authenticationYes
Mode selector switch1
Number of IO modules8 192
— Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
— of which in line, max.128
— per external encoder80
— per positioning axis80
— per synchronous axis160
— shortest clock pulse500 µs
Number of breakpoints8
Number of connections44
— HTTP request body, max.131 072 byte
— Sampling interval, min.100 ms
— Transmission rate, max.1 000 Mbit/s
Active power input, max.43 W; incl. ET 200SP modules and using USB
— for send cycle of 1 ms1 ms to 512 ms
— for send cycle of 2 ms2 ms to 512 ms
— for send cycle of 4 ms4 ms to 512 ms
— Number of sessions, max.48
Current consumption, max.2.9 A
Integrated power supplyYes
Number of SD card slots1
— Asset management recordYes; per user program
— for send cycle of 500 µs500 µs to 256 ms
— of which powerfail-proof300
— PROFINET Security ClassSNMP Configuration and DCP Read Only
— Publishing interval, min.200 ms
Number of elements (total)8 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements
Number of USB interfaces4; 2x USB 2.0, 2x USB 3.0 on front side
Product type designationCPU 1515SP PC2
— Number of program alarms200
— per speed-controlled axis40
— Number of connections, max.10
— Application authenticationYes
Number of RS 485 interfaces1; Via CM DP module
Reverse polarity protectionYes
SIMATIC memory card requiredNo
— Number of server methods, max.50
Number of PROFIBUS interfaces1; Via CM DP module
Number of PROFINET interfaces1
pre-installed operating systemWindows 10 IoT Enterprise 2016 LTSB, 64bit, MUI
— MRP interconnection, supportedYes; as MRP ring node according to IEC 62439-2 Edition 3.0
— of which status variables, max.200; per job
— Industrial Ethernet status LEDNo
— of which control variables, max.200; per job
Current consumption (rated value)1.8 A; Full processor load, incl. ET 200SP modules and using USB
— Number of server interfaces, max.10
Number of distributed IO systems20
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
— Number of registerable nodes, max.20 000
— Of which IO devices with IRT, max.64
Infeed power to the backplane bus8.75 W
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 10 engineering systems
— Number of IO Devices per tool, max.8
— Switchover time on line break, typ.200 ms; For MRP, bumpless for MRPD
— activation/deactivation of I-devicesYes; per user program
— GDS support (certificate management)Yes
— Number of accessible variables, max.100 000
— Number of stations in the ring, max.50
— Number of connectable IO Devices, max.128
— global warming potential, (total) [CO2 eq]432 kg
— number of simultaneous HTTP calls, max.4
— Number of alarms for system diagnostics100
— Number of subscriptions per session, max.50
automatic detection of transmission rateYes
Number of industrial Ethernet interfaces2
— Number of monitored items, recommended max.2 000; for 1 s sampling interval and 1 s send interval
Current consumption (in no-load operation), typ.0.5 A
Number of configurable program messages, max.10 000
— Number of connectable IO Devices for RT, max.128
— Number of inputs/outputs per server method, max.20
Number of simultaneously active program alarms1 000
— Number of IO Controllers with shared device, max.4
— global warming potential, (during operation) [CO2 eq]365 kg
— With IRT and parameterization of "odd" send cyclesUpdate time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)
— global warming potential, (during production) [CO2 eq]73.8 kg
Number of login stations for message functions, max.32
Retentive data area (incl. timers, counters, flags), max.410 kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Number of nodes for user-defined server interfaces, max.5 000
— global warming potential, (after end of life cycle) [CO2 eq]-6.71 kg
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— Number of nodes of the client interfaces, recommended max.2 000
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Number of inputs/outputs when calling OPC_UA_MethodCall, max.20
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— IO Devices changing during operation (partner ports), supportedYes
— Number of registerable method calls of OPC_UA_MethodCall, max.100
— Number of elements for one call of OPC_UA_MethodGetHandleList, max.100
— Number of elements for one call of OPC_UA_NameSpaceGetIndexList, max.20
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— Number of positioning axes at motion control cycle of 4 ms (typical value)30
— Number of positioning axes at motion control cycle of 8 ms (typical value)30
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Number of simultaneous calls of the client instructions for data access, per connection, max.5
— Number of elements for one call of OPC_UA_NodeGetHandleList/OPC_UA_ReadList/OPC_UA_WriteList, max.300
— Number of simultaneous calls of the client instructions for session management, per connection, max.1
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!