Weight, approx.1 200 g
Power loss, typ.20 W
primary/secondaryYes
Inrush current, max.63 A; Full width at half maximum 1 ms
Leakage current, max.5 mA
Overvoltage categoryII
Active power input, typ.95 W
Type of output voltageDC
Rated value at 120 V AC0.9 A
Rated value at 120 V DC1 A
Rated value at 230 V AC0.5 A
Rated value at 230 V DC0.5 A
Short-circuit protectionYes
Equipment protection classI, with protective conductor
for backplane bus (5 V DC), max.10 A; no base load required
for backplane bus (24 V DC), max.1 A; idling-proof
Design of electrical connection3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!