Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776
CounterYes
Jitter, max.1 µs
— Number, max.16
Rail mountingYes; S7-1500 mounting rail
Weight, approx.320 g
Current-sinkingYes; With High Speed output
Power loss, typ.5 W
Current-sourcingYes
— parameterizableYes; none / 0.05 / 0.1 / 0.4 / 0.8 ms
Number of outputs8; max. depending on parameterization
to SIMATIC S7-1500Yes
Diagnostics functionYes
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Bus cycle time (TDP), min.250 µs
Type of digital outputTransistor
Short-circuit protectionYes; electronic/thermal
Number of digital inputs8; max. depending on parameterization
Product type designationTM Timer DIDQ 16x24V
Number of digital outputs16; max. depending on parameterization
Controlling a digital inputYes
Substitute values connectableYes
Digital inputs, parameterizableYes
Digital outputs, parameterizableYes
from load voltage 1L+ (without load), max.40 mA; without load
from load voltage 2L+ (without load), max.30 mA; without load
Power consumption from the backplane bus1.3 W
Limitation of inductive shutdown voltage to-0.8 V
— permissible quiescent current (2-wire sensor), max.1.5 mA
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Input characteristic curve in accordance with IEC 61131, type 3Yes
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!