Weight, approx.31 g
Power loss, typ.0.85 W; Without encoder supply voltage
Rated value (DC)24 V
usable BaseUnitsBU type A0, A1
Automatic encodingYes
Diagnostics functionYes
Isolation tested with707 V DC (type test)
Measurement principleintegrating (Sigma-Delta)
between the inputs (UCM)10 V DC
Current consumption, max.37 mA; without sensor supply
Number of analog inputs4; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible
Product type designationAI 4x U/I 2-wire
— Input resistance (0 to 10 V)120 kΩ
Calibration possible in RUNNo
Cycle time (all channels), min.Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Reverse polarity protectionYes
— Input resistance (0 to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
— Input resistance (1 V to 5 V)120 kΩ
— Input resistance (-5 V to +5 V)120 kΩ
— Input resistance (-10 V to +10 V)120 kΩ
— Input resistance (4 mA to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
— Burden of 2-wire transmitter, max.650 Ω
Crosstalk between the inputs, min.50 dB
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reparameterization possible in RUNYes
Linearity error (relative to input range), (+/-)0.02 %
Temperature error (relative to input range), (+/-)0.005 %/K
Suitable for applications according to CQI-9Yes
Color code for module-specific color-coded labelCC03
Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
permissible input current for current input (destruction limit), max.50 mA
permissible input voltage for voltage input (destruction limit), max.30 V
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!