Weight, approx.31 g
data integrityYes; firmware V2.0.0 or higher
Power loss, typ.0.7 W; rated voltage, 50 % active channels, 50 % of range
Rated value (DC)24 V
usable BaseUnitsBU type A0, A1
Automatic encodingYes
Diagnostics functionYes
safely removing dataYes; firmware V2.0.0 or higher
Isolation tested with707 V DC (type test)
signed firmware updateYes; firmware V2.0.0 or higher
Current consumption, max.725 mA; worst case voltage, all channels active, max. load, no derating
Number of analog inputs8; Single-ended
Product type designationAI 8xI 2-/4-wire BA
Calibration possible in RUNNo
Cycle time (all channels), min.1 ms; per channel
Reverse polarity protectionYes
— Input resistance (0 to 20 mA)100 Ω; 15 bit
— Input resistance (4 mA to 20 mA)100 Ω; 15 bit
Current consumption (rated value)25 mA; rated voltage, all channels active, no load
— Burden of 2-wire transmitter, max.650 Ω
— Input resistance (-20 mA to +20 mA)100 Ω; 16 bit incl. sign
Crosstalk between the inputs, min.50 dB
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reparameterization possible in RUNYes
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Color code for module-specific color-coded labelCC01
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold, fungal and dry rot spores (excluding fauna)
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
permissible input current for current input (destruction limit), max.50 mA
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!