grid spacing60 mm
number of poles2
product versionN left
fastening methodDIN rail
RAL color number7 035
mounting positionany
installation depth70 mm
product brand nameSENTRON
degree of pollution2
product designationResidual current operated circuit breaker
protection class IPIP20, if the distribution board is installed, with connected conductors
design of the productInstantaneous
I2t value permissible58 000 A²·s
product type designation5SV3
RAL color number (similar)7 035
product feature silicon-freeYes
short-circuit current rating10 kA
number of modular width units2
position of power supply cordtop or bottom
let-through current permissible5 200 A
insulation voltage (Ui) rated value2 000 V
tripping fault current rated value30 mA
switching function short-term delayedNo
value range of the operating frequency50 Hz
value range of the supply voltage at AC230 V
ambient temperature during storage minimum-40 °C
value range of the supply voltage frequency50 Hz
supply voltage for testing equipment minimum195 V
mechanical service life (operating cycles) typical10 000
product extension installable supplementary devicesYes
size of installation devices according to DIN 438801
short-circuit current of series fuse maximum permissible63 A
number of test cycles for environmental testing according to IEC 60068-2-3028