— upwards20 mm
— forwards0 mm
— backwards0 mm
— downwards20 mm
trip classCLASS 10
— at the side9 mm
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
mounting positionany
— solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
product brand nameSIRIUS
product designationCircuit breaker
service life maximum10 a
— at 230 V rated value0 kW
— at 400 V rated value0.06 kW
— at 500 V rated value0.1 kW
— at 690 V rated value0.1 kW
design of the productFor motor protection
product type designation3RV1
size of the circuit-breakerS00
design of screwdriver shaftDiameter 5 to 6 mm
size of the screwdriver tipPozidriv size 2
Substance Prohibitance (Date)01/01/2013
design of the overload releasethermal
design of the short-circuit tripmagnetic
operating frequency rated value50 ... 60 Hz
operational current rated value0.2 A
product extension auxiliary switchYes
relative humidity during operation10 ... 95 %
device type according to ISO 13849-13
display version for switching statusRocker switch
surge voltage resistance rated value6 kV
reference code according to IEC 81346-2Q
test wear-related service life necessaryYes
number of poles for main current circuit3
type of voltage for main current circuitAC
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
product function short circuit protectionYes
safety device type according to IEC 61508-2Type A
number of CO contacts for auxiliary contacts0
number of NC contacts for auxiliary contacts0
number of NO contacts for auxiliary contacts0
electrical endurance (operating cycles) typical100 000
product function suitable for safety functionYes
size of contactor can be combined company-specificS00
type of voltage for auxiliary and control circuitAC/DC
overdimensioning according to ISO 13849-2 necessaryYes
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
B10 value with high demand rate according to SN 319205 000
installation altitude at height above sea level maximum2 000 m
protection class IP on the front according to IEC 60529IP20
failure rate [FIT] with low demand rate according to SN 3192050 FIT
arrangement of electrical connectors for main current circuitTop and bottom
response value current of instantaneous short-circuit trip unit2.6 A
insulation voltage with degree of pollution 3 at AC rated value690 V
adjustable current response value current of the current-dependent overload release0.14 ... 0.2 A