— solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
arcing time10 ... 15 ms
type of voltageAC
fastening methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 50022
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
size of contactorS00
— solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
product brand nameSIRIUS
product designationcapacitor contactors
product type designation3RT26
relative humidity minimum10 %
Substance Prohibitance (Date)05/01/2014
product extension auxiliary switchNo
electrical endurance (operating cycles)300 000
reference code according to IEC 81346-2Q
number of NC contacts for main contacts0
number of NO contacts for main contacts3
number of poles for main current circuit3
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
contact reliability of auxiliary contacts1e-8
apparent pick-up power of magnet coil at AC49 VA
apparent holding power of magnet coil at AC7.8 VA
number of NC contacts for auxiliary contacts1
number of NO contacts for auxiliary contacts1
type of voltage of the control supply voltageAC
control version of the switch operating mechanismStandard A1 - A2
type of calculation of power loss depending on polequadratic
contact rating of auxiliary contacts according to ULA600 / Q600
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
inductive power factor with closing power of the coil0.8
installation altitude at height above sea level maximum2 000 m
protection class IP on the front according to IEC 60529IP20
inductive power factor with the holding power of the coil0.25
operational current of auxiliary contacts at AC-12 maximum10 A
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
AWG number as coded connectable conductor cross section for main contacts20 ... 12
operational current at AC-6b at 690 V at ambient temperature 60 °C rated value18 A
design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 VC characteristic: 10 A; 0.4 kA
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1400 V